Industrial Automation Parts. Prompt replies from real people.

Schneider LC1D098T7 TeSys Deca Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider LC1D098T7?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1D098T7 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1D098T7
Material Number
—
Manufacturer
Schneider
Product ID
31215

Get a Free Quote

Request pricing and availability for LC1D098T7.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current
20 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
480 V AC 50/60 Hz
IP degree of protection
IP20 front face conforming to IEC 60529
See all specifications

Product Highlights

  1. Configuration: 4-pole contactor with 2 NO + 2 NC power poles and 1 NO + 1 NC auxiliary contacts
  2. Switching capacity: AC-1 resistive load rating of 20 A at up to 440 V AC and 140 °F (60 °C), with 25 A conventional free air thermal current for the power circuit
  3. Voltage ratings: power circuit up to 690 V AC (25...400 Hz) or 300 V DC, control circuit 480 V AC 50/60 Hz
  4. Durability: 15 million mechanical cycles and 0.6 million electrical cycles at 25 A AC-1 up to 440 V
  5. Terminations and mounting: screw clamp terminals for power and control circuits, 1.7 N·m tightening torque, plate or rail mounting, IP20 front face
LC1D098T7

Product Information

Technical Specifications

Specifications for LC1D098T7
ParameterValue
Product or component typeContactor
Range of productTeSys Deca
[Ue] rated operational voltagePower circuit: <= 690 V AC 25...400 Hz / Power circuit: <= 300 V DC
[Ie] rated operational current20 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage480 V AC 50/60 Hz
Control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Power dissipation per pole1.56 W AC-1
RangeTeSys
Connections - terminalsPower circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endPower circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endPower circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endPower circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable endControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable endControl circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Height85 mm
Width45 mm
Depth92 mm
IP degree of protectionIP20 front face conforming to IEC 60529
Permissible ambient air temperature around the device-40…60 °C / 60…70 °C with derating
Product certificationsCCCDNVRINAGOSTLROS (Lloyds register of shipping)GLULCSABV

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp