Industrial Automation Parts. Prompt replies from real people.

Schneider ATV71HC11YT High-Power AC Drive

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/25/2026

Q1Can you supply the Schneider ATV71HC11YT?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider ATV71HC11YT cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
ATV71HC11YT
Material Number
—
Manufacturer
Schneider
Product ID
29551

Get a Free Quote

Request pricing and availability for ATV71HC11YT.

More parts to source? Send your whole list in one enquiry

Key specifications

power supply voltage
500...690 V - 15...10 %
power supply voltage limits
425…759 V
Maximum Horse Power Rating
125 hp, 3 phase 575 V
power supply frequency
50...60 Hz - 5...5 %
Communication Port Protocol
CANopen / Modbus
IP degree of protection
IP41 on upper part EN/IEC 60529 / IP41 on upper part EN/IEC 61800-5-1 / IP54 on lower part EN/IEC 60529 / IP54 on lower part EN/IEC 61800-5-1 / IP00 EN/IEC 60529 / IP00 EN/IEC 61800-5-1 / IP30 on side parts EN/IEC 60529 / IP30 on side parts EN/IEC 61800-5-1 / IP30 on the front panel EN/IEC 60529 / IP30 on the front panel EN/IEC 61800-5-1
See all specifications

Product Highlights

  1. Power Ratings: 110 kW at 3-phase 690 V, 90 kW at 3-phase 500 V, and 125 hp at 3-phase 575 V
  2. Line and Output Current: Line current 113 A at 600 V, 117 A at 690 V, and 128 A at 500 V, nominal output current 125 A at 2.5 kHz for 575 V and 690 V, and 136 A at 2.5 kHz for 500 V
  3. Transient Capability: Maximum transient current 204 A for 60 s at 90 kW and 224.4 A for 2 s at 125 hp or 110 kW, transient overtorque 170% for 60 s every 10 minutes and 220% for 2 s
  4. Output Frequency and Switching: Output frequency 0.1...500 Hz, nominal switching frequency 2.5 kHz, adjustable 2.5...4.9 kHz with derating factor
  5. Power Supply: 500...690 V 3-phase, -15%...+10%, 50...60 Hz, with limits of 425...759 V and 47.5...63 Hz
  6. Motor Cable Length: Maximum 49.2 ft (15 m) shielded or 98.4 ft (30 m) unshielded
  7. Motor Control: Flux vector control with sensor, sensorless flux vector control, voltage/frequency ratio (2 or 5 points), and ENA system for unbalanced loads, supports asynchronous and synchronous motors
  8. Speed and Torque Accuracy: Speed accuracy +/- 0.01% of nominal speed in closed-loop mode with encoder feedback and +/- 10% of nominal slip without speed feedback, torque accuracy +/- 5% closed-loop and +/- 15% open-loop
  9. Braking Torque: Up to 150% with braking or hoist resistor and 30% without braking resistor
  10. Communications: Modbus and CANopen protocols with RS 485 and CANopen physical interfaces
  11. I/O and Analog Signals: 7 discrete inputs, 2 analog inputs, 1 analog output, and 2 relay outputs
  12. Protection and Compliance: Integrated EMC filter, CE marking, UL Type 1, and IEC 61800-3 environments 1 and 2 category C3
  13. Ambient and Installation: Operating temperature 14...122 °F (-10...50 °C) without derating, storage -13...158 °F (-25...70 °C), relative humidity 5...95% without condensation, operating altitude up to 3280.84 ft (1000 m) without derating
  14. Dimensions and Weight: 46.9 in (1190 mm) high, 14.8 in (377 mm) deep, 13.4 in (340 mm) wide, 255.7 lb (116 kg)
ATV71HC11YT

Product Information

Technical Specifications

Specifications for ATV71HC11YT

ParameterValue
Product or Component TypeVariable speed drive
Range of ProductAltivar 71
power supply voltage500...690 V - 15...10 %
power supply voltage limits425…759 V
Maximum Horse Power Rating125 hp, 3 phase 575 V
Motor power kW110 kW, 3 phase 690 V / 90 kW, 3 phase 500 V
power supply frequency50...60 Hz - 5...5 %
Communication Port ProtocolCANopen / Modbus
Electrical connectionTerminal 2.5 mm², AWG 14 AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)Terminal 2 x 120 mm² L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)Terminal 120 mm² PA, PB)Terminal 2 x 120 mm² PC/-, PO, PA/+)
Height46.9 in (1190 mm)
ParameterValue
Width13.4 in (340 mm)
Depth14.8 in (377 mm)
IP degree of protectionIP41 on upper part EN/IEC 60529IP41 on upper part EN/IEC 61800-5-1IP54 on lower part EN/IEC 60529IP54 on lower part EN/IEC 61800-5-1IP00 EN/IEC 60529IP00 EN/IEC 61800-5-1IP30 on side parts EN/IEC 60529IP30 on side parts EN/IEC 61800-5-1IP30 on the front panel EN/IEC 60529IP30 on the front panel EN/IEC 61800-5-1
Ambient air temperature for operation14…122 °F (-10…50 °C) (without derating)
Product CertificationsGOSTCSANOM 117ULC-tick