Product Model
vaem-l1-s-24-ap
Material Number
8081923
Manufacturer
Festo
Product ID
16904

Get a Free Quote

Request pricing and availability for vaem-l1-s-24-ap.

More parts to source? Send your whole list in one enquiry

Key specifications

Diagnose per internal communication
Load switch-off Electronics/sensors overvoltage Load overvoltage Electronics/sensors undervoltage Load undervoltage
Reverse polarity protection
yes
Intrinsic current consumption at nominal operating voltage for electronics/sensors
Typically 34 mA
Intrinsic current consumption at nominal operating voltage load
Typically 22 mA
Ambient temperature
-5°C – 60°C
Product weight
76g
See all specifications

Product Highlights

  1. Valve Capacity: Supports up to 24 valve positions and up to 48 solenoid coils
  2. Diagnostics: Per-module LED indication of load power supply, load switch-off, electronics/sensors overvoltage, load overvoltage, electronics/sensors undervoltage, and load undervoltage
  3. Power Supply: 24 V DC for electronics/sensors and load, maximum supply 2 x 4 A with external fuse required, M8x1 A-coded 4-pin plug and socket for incoming and forwarded supply
  4. Protection and Operating Conditions: IP65 and IP67 in mounted state with unused connections sealed, ambient temperature -5°C to 60°C, storage temperature -20°C to 60°C, relative air humidity 5 to 95 % non-condensing
  5. Communication and Compliance: AP-COM system communication via 2x M8x1 D-coded 4-pin sockets, maximum system communication cable length 50 m, CE and UKCA EMC marking, c UL us Recognized, RCM, KC EMC, RoHS-compliant
vaem-l1-s-24-ap

Product Information

Technical Specifications

Specifications for vaem-l1-s-24-ap

ParameterValue
Dimensions W x L x H42 mm x 91 mm x 30 mm
Connection positionTop
Diagnostics via LEDDiagnostics per module Load power supply
Diagnose per internal communicationLoad switch-off Electronics/sensors overvoltage Load overvoltage Electronics/sensors undervoltage Load undervoltage
Max. no. of valve positions24
Max. no. of solenoid coils48
Reverse polarity protectionyes
Module parametersConfiguration of voltage monitoring, load supply PL Response in error state
Fuse protection (short circuit)Internal electronic fuse per channel
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 34 mA
Intrinsic current consumption at nominal operating voltage loadTypically 22 mA
Nominal operating voltage DC for electronics/sensors24V
Nominal operating voltage DC load24V
Power failure buffering10ms
Power failure buffering of load3ms
Permissible voltage fluctuations for electronics/sensors± 25 %
Permissible voltage fluctuations load± 10%
Max. power supply2 x 4 A (external fuse required)
Power supply, functionIncoming electronics/sensors and load
Power supply, type of connectionPlug
Power supply, connection technologyM8x1, A-coded as per EN 61076-2-104
Power supply, number of pins/wires4
Voltage forwarding, functionOutgoing electronics/sensors and load
Voltage forwarding, connection typeSocket
ParameterValue
Voltage forwarding, connection technologyM8x1, A-coded as per EN 61076-2-104
Voltage forwarding, number of pins/wires4
Communication interface, connection type2x socket
Communication interface, connection technologyM8x1, D-coded as per EN 61076-2-114
Communication interface, number of pins/wires4
Communication interface, functionSystem communication XF10 IN / XF20 OUT
Communication interface, protocolAP-COM
Communication interface, shieldingyes
CE marking (see declaration of conformity)As per EU EMC directive
UKCA marking (see declaration of conformity)To UK instructions for EMC
KC charactersKC EMC
Max. cable length50 m system communication
Corrosion resistance class (CRC)2 - Moderate corrosion stress
LABS (PWIS) conformityVDMA24364-B1/B2-L
Storage temperature-20°C – 60°C
Relative air humidity5 - 95 % Non-condensing
Protection against direct and indirect contactPELV SELV
Note regarding operating voltageSELV/PELV fixed power supplies required Note voltage drop
Degree of protectionIP65 IP67
Note on degree of protectionIn mounted state Unused connections sealed
Ambient temperature-5°C – 60°C
CertificationRCM compliance mark c UL us - Recognized (OL)
Nominal altitude of use above sea level<= 2000 m NHN
Product weight76g
Type of mountingScrewed tightly
Housing materialPA-reinforced
Threaded sleeve materialBrass, nickel-plated
Note on materialsRoHS-compliant
Manufacturer ID8081923