Product Model
7MF1565-3BA00-1AA1
Material Number
7mf15653ba001aa1
Manufacturer
SIEMENS
Product ID
119866

Get a Free Quote

Request pricing and availability for 7MF1565-3BA00-1AA1.

More parts to source? Send your whole list in one enquiry

Key specifications

Measuring range for gauge pressure
0 ... 1 bar (0 ... 14.5 psi)
Minimum overload limit
-1 bar (-14.5 psi)
Maximum overload limit
2.5 bar (36.26 psi)
Explosion protection
None
Ambient temperature
-25 ... +85 °C (-13 ... +185 °F)
Weight
Approx. 0.090 kg (0.198 lbs)
See all specifications
7MF1565-3BA00-1AA1

Product Information

Technical Specifications

Specifications for 7MF1565-3BA00-1AA1

ParameterValue
Measuring range for gauge pressure0 ... 1 bar (0 ... 14.5 psi)
Minimum overload limit-1 bar (-14.5 psi)
Maximum overload limit2.5 bar (36.26 psi)
Burst pressure> 2.5 bar (> 36.3 psi)
Output signal4 ... 20 mA; 2-wire system; auxiliary power 7 ... 33 V DC (10 ... 30 V DC for ATEX devices)
Explosion protectionNone
Electrical connectionPlug according to EN 175301-803-A, stuffing box thread M16 (with coupling)
Process connectionG1/2" male according to EN 837-1 (1/2" BSP male)
Gasket material between sensor and enclosureViton (FPM, standard)
ParameterValue
VersionStandard version
Measuring principlePiezoresistive measuring cell (ceramic diaphragm)
Measurement deviation at limit setting (typical)0.25% of measuring span
Step response time T99< 5 ms
Long-term stability0.25% of measuring span/year
Ambient temperature-25 ... +85 °C (-13 ... +185 °F)
Storage temperature-50 ... +100 °C (-58 ... +212 °F)
Degree of protectionIP65 with plug according to EN 175301-803-A
WeightApprox. 0.090 kg (0.198 lbs)
Material of wetted parts (measuring cell)Al2O3 - 96%
Process temperature (with FPM gasket)-15 ... +125 °C (5 ... 257 °F)