Industrial Automation Parts. Prompt replies from real people.

ABB OT200ES03 Isolating switch

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/24/2026

Q1Can you supply the ABB OT200ES03?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ABB OT200ES03 cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
OT200ES03
Material Number
—
Manufacturer
ABB
Product ID
1175091

Get a Free Quote

Request pricing and availability for OT200ES03.

More parts to source? Send your whole list in one enquiry

Key specifications

Degree of Protection
Front IP00
Product Net Weight
1.5 kg
Rated Conditional Short-Circuit Current (I<sub>nc</sub>)
(315 A fuse, 500 V) 100 kA (355 A fuse, 690 V) 80 kA (250 A fuse, 690 V) 100 kA
Rated Impulse Withstand Voltage (U<sub>imp</sub>)
12 kV
Rated Insulation Voltage (U<sub>i</sub>)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Power AC-23A (P<sub>e</sub>)
(220 ... 240 V) 60 kW (400 ... 415 V) 110 kW (500 V) 132 kW (690 V) 200 kW
See all specifications
OT200ES03

Product Information

Technical Specifications

Specifications for OT200ES03

ParameterValue
Degree of ProtectionFront IP00
Environmental Information1SCC301265D0201
Pollution Degree3
Product Net Width181.5 mm
Product Net Height150 mm
Product Net Depth / Length82.5 mm
Product Net Weight1.5 kg
Conventional Free-air Thermal Current (I<sub>th</sub>)Θ = 40 °C 200 A
Conventional Thermal Current (I<sub>the</sub>)Fully Enclosed 200 A
Degree of ProtectionFront IP00
Distance Between PhasesStandard
Handle TypeHandle and shaft not included
Lock TypeNo
Mechanical Durability20000
Mounting TypeBase mounting
Number of Poles3P
Operating ModeSide operated
Pollution Degree3
Position of Line TerminalsTop In - Bottom Out Bottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 4.0 W
Rated Conditional Short-Circuit Current (I<sub>nc</sub>)(315 A fuse, 500 V) 100 kA (355 A fuse, 690 V) 80 kA (250 A fuse, 690 V) 100 kA
Rated Impulse Withstand Voltage (U<sub>imp</sub>)12 kV
Rated Insulation Voltage (U<sub>i</sub>)acc. to IEC/EN 60664-1 1000 V
ParameterValue
Rated Operational Current AC-21A (I<sub>e</sub>)(380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A
Rated Operational Current AC-22A (I<sub>e</sub>)(380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A
Rated Operational Current AC-23A (I<sub>e</sub>)(380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A
Rated Operational Power AC-23A (P<sub>e</sub>)(220 ... 240 V) 60 kW (400 ... 415 V) 110 kW (500 V) 132 kW (690 V) 200 kW
Rated Operational VoltageMain Circuit 1000 V
Rated Short-Circuit Making Capacity (I<sub>cm</sub>)(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (I<sub>cw</sub>)for 1 s 8 kA
Special FunctionsNo
StandardsIEC 60947-3
Switches Operating MechanismMechanism at the End of the Switch 03 (Left Side)
Terminal TypeLug terminals
Tightening Torqueacc. IEC 60947-1 15 … 22 N·m
Tightening Torqueacc. IEC 60947-1 15 … 22 N·m
Object Classification CodeQ
ETIM 8EC000216 - Switch disconnector
ETIM 9EC000216 - Switch disconnector (low voltage)
UNSPSC39122233
IDEA Granular Category Code (IGCC)5290 >> Disconnect switch
eClassV11.1 : 27371403
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)3661701
Manufacturer ID1SCA022860R0200

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.