Industrial Automation Parts. Prompt replies from real people.

Schneider LC1F3304ED TeSys F Contactor

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the Schneider LC1F3304ED?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the Schneider LC1F3304ED cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
LC1F3304ED
Material Number
—
Manufacturer
Schneider
Product ID
111054

Get a Free Quote

Request pricing and availability for LC1F3304ED.

More parts to source? Send your whole list in one enquiry

Key specifications

[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current
400 A (at <40 °C) at <= 440 V AC AC-1
[Uc] control circuit voltage
48 V DC
IP degree of protection
IP20 front face with shrouds conforming to IEC 60529 / IP20 front face with shrouds conforming to VDE 0106
See all specifications

Product Highlights

  1. Product Type: TeSys F 4-pole AC-1 contactor for resistive loads, rated 400 A at 40 °C and up to 440 V AC
  2. Contact Configuration: 4 NO power poles with 48 V DC control circuit, closing time 40 to 50 ms and opening time 40 to 65 ms
  3. Switching Capacity: 2640 A rated breaking capacity per IEC 60947-4-1, 8 kV impulse withstand, 1000 V AC / 460 V DC operational voltage
  4. Durability: 10 million mechanical cycles and maximum operating rate of 2400 cycles per hour at 55 °C
  5. Compliance and Environment: IEC 60947-4-1, EN 60947-4-1, JIS C8201-4-1, UL, CSA, RoHS and REACH, with TH protective treatment and IP20 front face
LC1F3304ED

Product Information

Technical Specifications

Specifications for LC1F3304ED

ParameterValue
Product or component typeContactor
Range of productTeSys F
[Ue] rated operational voltage<= 1000 V AC 50/60 Hz / <= 460 V DC
[Ie] rated operational current400 A (at <40 °C) at <= 440 V AC AC-1
[Uc] control circuit voltage48 V DC
Control circuit voltage limitsOperational: 0.85...1.1 Uc (at 55 °C) / Drop-out: 0.15...0.2 Uc (at 55 °C)
Power dissipation per pole44 W AC-1
RangeTeSys
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable endControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable endControl circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable endControl circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable endPower circuit: lugs-ring terminals 1 cable(s) 240 mm²Power circuit: bar 2 cable(s) - busbar cross section: 30 x 5 mmPower circuit: bolted connection
ParameterValue
Height206 mm
Width261 mm
Depth219 mm
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 / IP20 front face with shrouds conforming to VDE 0106
Ambient air temperature for operation-5…55 °C
Product certificationsRINALROS (Lloyds register of shipping)RMRoSULCBCCCDNVBVABS

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.

Need Help Checking This Part?

Ask about specifications, condition or a suitable alternative.

Contact Us on WhatsApp
WhatsApp