Product Model
1756-IF8IH
Material Number
—
Manufacturer
ROCKWELL
Product ID
108556

Get a Free Quote

Request pricing and availability for 1756-IF8IH.

More parts to source? Send your whole list in one enquiry

Key specifications

Input, voltage
Yes
Terminal block torque specifications
1756-TBCH: 0.5 Nm (4.4 in-lb)
Input overvoltage protection
28.8V DC
Operating temperature
0 °C <Ta <60 °C (32 °F <Ta <140 °F)
Weight
0.379
See all specifications

Product Highlights

  1. 8-Channel Analog Input: Eight isolated differential current inputs support 0-20 mA and 4-20 mA signals with configurable input ranges of 0-20.58 mA and 3.42-20.58 mA
  2. HART Communication: Supports HART digital communication with a typical update time of 1 s for all channels when HART is enabled
  3. Resolution and Accuracy: 16 to 21-bit resolution via a 24-bit Sigma-Delta ADC with calibrated accuracy of 0.15 to 1.5 percent of full scale depending on filter and HART settings
  4. Isolation and Protection: 250 V continuous reinforced insulation from inputs to backplane and 28.8 V DC input overvoltage protection
  5. Open-Circuit Detection: Detects open circuits in the 4-20 mA range within 5 s and reports a negative full-scale value
1756-IF8IH

Product Information

Technical Specifications

Specifications for 1756-IF8IH

ParameterValue
Input Signal0-20mA, 4-20mA
Isolation250V (continuous), reinforced insulation type, inputs to backplane
Number Of Channels8
Input, currentYes
Input, voltageYes
Input, resistorNo
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableYes
Output, currentNo
Output, voltageNo
Output signal configurableNo
Analogue inputs configurableYes
Analogue outputs configurableNo
Type of electric connectionScrew-/spring clA connection
Input offset drift with temperature<=300 μA/°C
Wire typeCopper
Terminal block torque specifications1756-TBCH: 0.5 Nm (4.4 in-lb)
Inrush current400mA @ 5V, 450mA @ 24V
Input conversion methodSigma-Delta ADC (24-bit converter)
Module keyingElectronic, software configurable
Module error over full temperature range0.3% of range (all filters) with HART disabled
Input range0...20 mA (0...20.58 mA), 4...20 mA (3.42...20.58 mA)
Data format32-bit floating point
Wire category2 - on signal ports
Common mode noise rejection>90 dB @ 50/60 Hz (10 Hz, 15 Hz or 20 Hz filters only)
Normal mode noise rejection>90 dB @ 50 Hz and 60 Hz with 10 Hz filter, >74 dB @ 50 Hz and 60 Hz with 15 Hz filter, >33 dB @ 50 Hz and >90 dB @ 60 Hz with 20 Hz filter
Gain drift with temperature20 ppm/°C
Voltage and current ratingsBackplane: 210mA @ 5.1V DC, 110mA @ 24V DC, Input voltage range: 5...30V DC, Input current range: 0...20mA @ 4...20mA
Typical module HART dynamic variables update time for all channels1 s typical if all channels are HART enabled Pass through messages, handheld communications, sary masters, communication errors, or configuration changes can significantly increase the update time.
Module scan time18...488 ms (filter dependent) for all channels - analog, minimum
InputsEight current inputs
Resolution16 to 21 bit
ParameterValue
Wire sizeSingle wire connection (1756-TBCH): 0.33...2.1 mm2 (22...14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation maximum, Single wire connection (1756-TBS6H): 0.33...2.1 mm2 (22...14 AWG) solid or
Calibrated accuracy0.15...1.5% of full scale, filter dependent@ 25 °C with HART disabled, 1.5% of full scale with 250 Hz filter @ 25 °C with HART enabled, 0.5% of full scale with 100 Hz filter @ 25 °C with HART enabled, 0.2% of full scale with 50 Hz or 60 Hz filter @ 25 °C
Open circuit detection time5 s (4...20 mA range only)
Suitable for safety functionsNo
Power dissipation within module4 W
Input overvoltage protection28.8V DC
Surrounding air temperature, max60 °C
North American temperature codeT5
EmissionsIEC 61000-6-4
ESD immunity6 kV contact discharges, 8 kV air discharges
EFT/B immunity±2kV @ 5kHz on signal ports
Relative humidity5...95% noncondensing
Conducted RF immunity10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz on shielded signal ports
Surge transient immunity±2 kV line-earth (CM) on shielded signal ports
Operating temperature0 °C <Ta <60 °C (32 °F <Ta <140 °F)
Radiated RF immunity10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Nonoperating temperature-40 °C
RTB keyingUser-defined mechanical
Vibration2 G @ 10...500 Hz
ShockOperating: 30 G, Non operating: 50 G
Slot width1
Calibration interval12 mo typical
ATEX temperature codeT4
IECEx temperature codeT4
Input impedance250 ? ±5 ?
Isolation voltage250V (continuous), Reinforced insulation type, inputs to backplane, Basic insulation type, input to input, and inputs to ground.
Enclosure type ratingNone (open-style)
RepairableREPAIRABLE
Preferred Availabilitytrue
Quick Turnaroundfalse
Dimension Height5.461
Lead Time5
Dimension Width18.288
Dimension Length21.844
Stock StatusSTOCKED
Weight0.379
Weight UnitKG
Dimension UnitCM

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.