Industrial Automation Parts. Prompt replies from real people.

ROCKWELL 1756-OF8IH ControlLogix PLC

  • Warehouse stock, ready to ship
  • Fully genuine original parts
  • Free quotes within 24 hours
Get a Free Quote

Free quote · Reply within 24 hours

Last Updated: 11/26/2026

Q1Can you supply the ROCKWELL 1756-OF8IH?

Yes. Stock comes from our own warehouse and a wide partner supplier network, including discontinued models — confirmed on enquiry.

Q2What will the ROCKWELL 1756-OF8IH cost me?

Every enquiry gets the best market price we can offer at that moment, by email and WhatsApp together, usually within 24 hours.

Q3Are your products genuine?

Yes. Genuine original parts only — we refuse counterfeit or imitation products. Condition confirmed in writing.

Product Model
1756-OF8IH
Material Number
—
Manufacturer
ROCKWELL
Product ID
107118

Get a Free Quote

Request pricing and availability for 1756-OF8IH.

More parts to source? Send your whole list in one enquiry

Key specifications

Input, voltage
Yes
Terminal block torque specifications
1756-TBCH: 0.5 Nm (4.4 in-lb)
Overvoltage protection
±24V DC
Operating temperature
0 °C <Ta <60 °C (32 °F <Ta <140 °F)
Weight
0.408
See all specifications

Product Highlights

  1. 8-Channel Current Output: Provides 8 current outputs with a 4-20 mA signal range and a 0-20 mA output range
  2. Output Accuracy and Resolution: Calibrated accuracy of 0.15% at 4-20 mA at 25 °C and 15-bit resolution across 24 mA
  3. Isolation: 250 V continuous isolation with reinforced insulation from outputs to backplane and basic insulation between outputs and to ground
  4. HART Timing: Settling time is under 23 ms to 95% with resistive loads when HART is disabled and under 100 ms when HART is enabled
  5. Load and Protection: Drives 50 to 750 ohm loads with short circuit survival and output short circuit protection electronically limited to 21 mA or less
  6. Power and Environment: Draws 400 mA at 24 V DC with 6.5 W nominal maximum power dissipation and operates from 0 to 60 °C
1756-OF8IH

Product Information

Technical Specifications

Specifications for 1756-OF8IH

ParameterValue
Isolation250V (continuous), Reinforced insulation type, outputs to backplane. Basic insulation type, output to output, and outputs to ground.
Number Of Channels8
Output Signal4-20mA
Input, currentYes
Input, voltageYes
Input, resistorNo
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableYes
Output, currentNo
Output, voltageNo
Output signal configurableNo
Analogue inputs configurableYes
Analogue outputs configurableNo
Type of electric connectionScrew-/spring clA connection
Wire typeCopper
Output range0...20mA @ 4...20mA
Load reactance10 μH maximum
Terminal block torque specifications1756-TBCH: 0.5 Nm (4.4 in-lb)
Module keyingElectronic, software configurable
Offset drift±3 ppm of full scale range/°C (72 nA/°C typical)
Output conversion methodR-Ladder DAC
Outputs8 current
Open circuit detectionCurrent output only (output must be set >=0.1 mA)
Drive capability50...750 ? with short circuit survival
Data formatIEEE 32-bit floating point
Wire category2 - on signal ports
Overvoltage protection±24V DC
Module error0.3% @ 4...20mA
Gain drift with temperature±4 ppm of full scale range/°C
Voltage and current ratingsBackplane: 220mA @ 5.1V DC, 360mA @ 24V DC, Output voltage range: 5...30V DC, Output current range: 0...20mA @ 4...20mA
Settling timeHART not enabled: <23 ms to 95% with resistive loads, HART enabled: <100 ms to 95% with resistive loads
Module scan timeEstimate 1 s if all channels are HART enabled, Pass through messages, handheld communications, sary masters, communication errors, or configuration changes can significantly increase the update time.
Current draw400 mA (estimated) @ 24V @ 24V
ParameterValue
Power dissipation6.5 W nominal (maximum), (<6.4 W with 50 ? load on all channels), (<6.5 W with 250 ? load on all channels), (<6.7 W with 750 ? load on all channels)
Resolution15 bit across 24 mA, 732 nA per bit
Wire sizeSingle wire connection (1756-TBCH): 0.33...2.1 mm2 (22...14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation maximum, Single wire connection (1756-TBS6H): 0.33...2.1 mm2 (22...14 AWG) solid or
Calibrated accuracy0.15% @ 4...20mA, 25 °C (77 °F)
Suitable for safety functionsNo
Output short circuit protectionCurrent electronically limited to <=21 mA with no damage
Surrounding air temperature, max60 °C
North American temperature codeT4A
EmissionsIEC 61000-6-4
ESD immunity6 kV contact discharges, 8 kV air discharges
EFT/B immunity±2kV @ 5kHz on signal ports
Relative humidity5...95% noncondensing
Conducted RF immunity10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Surge transient immunity±2kV line-earth (CM) on shielded ports
Operating temperature0 °C <Ta <60 °C (32 °F <Ta <140 °F)
Radiated RF immunity10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Nonoperating temperature-40 °C
RTB keyingUser-defined mechanical
Vibration2 G @ 10...500 Hz
ShockOperating: 30 G, Non operating: 50 G
Slot width1
Calibration interval12 mo typical
ATEX temperature codeT4
IECEx temperature codeT4
Isolation voltage250V (continuous), Reinforced insulation type, outputs to backplane, Basic insulation type, output to output, and outputs to ground.
Enclosure type ratingNone (open-style)
RepairableREPAIRABLE
Preferred Availabilitytrue
Quick Turnaroundfalse
Dimension Height5.334
Lead Time5
Dimension Width18.542
Dimension Length23.876
Stock StatusSTOCKED
Weight0.408
Weight UnitKG
Dimension UnitCM

Specifications may change. Confirm the exact model, revision and offered condition with your quotation.