- 150-F25FCDB-20E-HC3
The Rockwell 150-F25FCDB-20E-HC3 is a smart motor controller. Its stated voltage rating is 600 V AC. A second parameter lists a current value of 100 V AC; because the unit is volts rather than amperes, this value is omitted as inconsistent. The controller is supplied in a NEMA Type 4/12 (IP65) enclosure. It is classified as not repairable. Dimensions are listed as 0.0 for height, width, and length, and weight is 0.999 KG. Stock status is non-stocked, preferred availability is false, quick turnaround is false, and lead time is 29. No manufacturer part number or order code is supplied.
- 150-F25NBD
The Rockwell Allen-Bradley 150-F25NBD is a SMC Flex soft starter with an integrated display. It is rated 25 A and 5–15 Hp at 460V AC, with a maximum line-connected motor power of 7.5Hp at 230V AC, 60 Hz, three-phase. Control voltage is 100...240V AC; the transformer control module draws 75VA at 100...240V AC (-15%, +10%). The power circuit operates at 50/60 Hz, with a repetitive peak inverse voltage rating of 1400V per UL/CSA/NEMA and RC snubber DV/DT protection. Trip classes are 10, 15, 20 and 30, with trip current at 117% of motor FLC. Overload current is 5 A for line-connected and 8.6 A for delta-connected devices. Control options: none.
- 150-F25NBDB
The Rockwell 150-F25NBDB is a 25 A soft starter in the SMC Flex product family, rated 5–15 Hp at 460 V AC. It operates on 200–480 V AC, 3-phase, 50/60 Hz power, with a control voltage of 100–240 V AC. The controller includes a display and supports pump control. Trip classes are 10, 15, 20, and 30, with a trip current rating of 117% of motor FLC. Overload current is 5 A for line-connected devices and 8.6 A for delta-connected devices. Maximum line-connected motor power is 7.5 Hp at 230 V AC, 60 Hz, 3-phase. The power circuit includes an RC snubber network for DV/DT protection and a repetitive peak inverse voltage rating of 1400 V per UL/CSA/NEMA.
- 150-F25NBR
The Rockwell Allen-Bradley 150-F25NBR is a SMC Flex soft starter with an integrated display. It is rated 25 A and 5-15 Hp at 460 V AC, with a line-connected motor power maximum of 7.5 Hp at 230 V AC, 60 Hz, three-phase. Control voltage is 24 V AC/DC; rated control supply voltage is 24 V at both 50 Hz and 60 Hz. The power circuit operates at 50/60 Hz with a rated operating voltage Ue of 200 V. Overload current is 5 A for line-connected devices and 8.6 A for delta-connected devices. Trip classes are 10, 15, 20, and 30, with trip current rating 117% of motor FLC. Control options are none.
- 150-F25NBRB
The Rockwell 150-F25NBRB is an SMC Flex soft starter with a 25 A controller rating and 5–15 Hp at 460 V AC. It uses 24 V AC/DC control voltage, with rated control supply voltage of 24 V at both 50 Hz and 60 Hz. The power circuit operates at 50/60 Hz, and the rated operating voltage Ue is 200. Line-connected motor power is 7.5 Hp at 230 V AC, 60 Hz, three-phase. Overload current is 5 for line-connected devices and 8.6 for delta-connected devices. Trip classes are 10, 15, 20, and 30, with trip current rating 117% of motor FLC. Control options include pump control, and a display is included.
- 150-F25NBRD
The Rockwell 150-F25NBRD is a SMC Flex soft starter with an integrated display. It is rated 25 A and 5–15 Hp at 460 V AC, with a maximum line-connected motor power of 7.5 Hp at 230 V AC, 60 Hz, three-phase. Control voltage is 24 V AC/DC; rated control supply voltage is 24 V at both 50 Hz and 60 Hz. The controller provides selectable trip classes 10, 15, 20, and 30, and a trip current rating of 117% of motor full load current. Overload current is 5 A for line-connected devices and 8.6 A for delta-connected devices. Power-circuit operating frequency is 50/60 Hz. The power circuit includes an RC snubber network for DV/DT protection and a repetitive peak inverse voltage rating of 1400 V per UL/CSA/NEMA.
- 150-F25NCD
The ROCKWELL 150-F25NCD is an SMC Flex soft starter for three-phase motor control, rated 25 A and 5-15 Hp at 460V AC. Control voltage is 100...240V AC. The controller includes an LCD display and keypad. Power circuit operating frequency is 50/60 Hz, with rated operational voltage 200...600V AC (-15%, +10%) per UL/CSA/NEMA. Line connected motor current is 5...25A at 500/575V AC, three-phase; delta connected motor current is 8.7...43A at 500/575V AC, three-phase. Integrated motor overload protection is included, with trip classes 10, 15, 20 and 30. Enclosure is open type, IP20 per IEC for the power circuit. Operating temperature is -5 to 50 degrees C (23 to 122 degrees F).
- 150-F317NBD
The Rockwell 150-F317NBD is an SMC Flex soft starter with an integrated display and internal bypass. It is rated 317 A and 125–250 hp at 460 V AC, with a control voltage of 100...240 V AC. Line-connected motor current is 106...317 A at 600/Y/690 V AC, 3-phase; delta-connected motor current is 183...549 A at 500/575 V AC, 3-phase. The controller provides integrated motor overload protection, trip classes 10, 15, 20 and 30, and a trip current rating of 117% of motor FLC. It has four programmable NO/NC auxiliary contacts. Operating temperature is -5 to 50 °C open type, at altitudes up to 2000 m, pollution degree 2.